Head Calculation For Irrigation Booster Pump

 

Station No. Valve Size of Valve Controller’s Program flow in lps Duration (min) Total flow as
per specified duration (litres/day)
1 DV – 1 1″ A 0.72 60 2592
2 DV  -2 1″ A 0.05 60 180
2772
Total run time 2 hrs
Total Water Requirement – 2.6  m3/day

Maximum flow of the system: 2.6 m3 per hour (Considering water window of 1 hr/day)

Head Loss Calculation in Main Line

  • Head loss of the Total Main Line Length to a Valve can be taken as Main Line Loss for Total Head Loss Calculation.
  • The length of Main Line to a Valve (DV2) = m
Sl.No Main Line Length in m Flow in the Section, in lps Size of the Pipe Head Loss in (Mtr)  from Pipe Characteristic Sheet
1 A -B 59 0.05 1.5” 0.01
2 B –C 8 0.05 1.5” 0.005
  Total Loss 0.011

(Note; friction loss is calculated as per the Darcy–Weisbach equation  formula uPVC pipe Class E)

Head Loss Calculation in Solenoid Valve

  • Head loss of the Highest Elevation end point Flow under a Valve can be taken as Solenoid Valve Loss for Total Head Loss Calculation.
  • The Maximum Flow of Solenoid Valve (DV2) = 0.05 lps
Sl.No Solenoid Valve Flow in the Section, in lps Size of Valve Head Loss in (Mtr) from Valve Characteristic Sheet
1 DV02 0.05 1” 0.138

The length of lateral Line of Valve (DV 02) = m

Sl.No Lateral Line Length in m Flow in the Section, in lps Size of the Pipe Head Loss in (Mtr)  from Pipe Characteristic Sheet
1 a– b 46 0.05 1” 0.05
2 b – c 7.40 0.05 1” 0.012
3 c – d 25 0.05 1” 0.032
  Total Loss 0.094                                                 

(Note: Friction loss is calculated as per the Darcy–Weisbach equation  formula uPVC pipe Class E)

Total Head Requirement of irrigation systemirrigation booster pump head calculation

  • Head Loss due to Elevation difference from the Pump Room to irrigation System = 10.95 m.
  • Head loss due to Pump Room Fittings can be considered as 5.0 m.
  • Maximum Head Loss due to Pipe Fittings (Main line & Lateral lines) can be considered as 3.0 m.

Total Head Loss Calculation:

Sl.No Item Description Head Loss
1 Minimum Required operating Pressure for Drip  Irrigation System 20.0 m
2 Head Loss in Main Line 0.011 m
3 Head Loss in Lateral Line 0.094 m
4 Head Loss in Solenoid Valve 0.14 m
5 Head Loss Due to the Fittings of  Pump Room 5.00 m
6 Head Loss Due to Screen filter 2.00 m
7 Head Loss Due to Elevation Difference 10.95 m
8 Head Loss due to fittings in main line 3.00 m
  Total Head Loss 41.19 m
Safety Factor @ 10%       6.17 m
  Head Required for the Pump 47.36 m

Flow of the system –  2.6 m3/hr  

15% safety factor  –  0.39 m3/hr

Flow of pump -2.99m3/hr

The duty point of the pump should be 2.99 m3/hr @ 48 m head.


Discover more from Method Statement HQ

Subscribe to get the latest posts to your email.

error: Content is protected !!