Web Master

main-distribution-board MDB Testing Procedure

Main Distribution Board MDB Testing & Commissioning Procedure

Upon completion of the LV Distribution Board installation including proper terminations into each breaker, the same shall be offered up for inspection from consultants. Earth fault loop impedance test & earth leakage test for LV Distribution Board shall be done & recorded in prescribed format. There are 3 cases to be considered. Case 1 is […]

Main Distribution Board MDB Testing & Commissioning Procedure Read More »

Electrical Method Statements, Method Statements, Testing & Commissioning

Condensate Water Filter Installation Method Statement

The Condensate Water Filter (Side Stream/ Multimedia) are compact filtration packages for the removal of grit, airborne particles and scale from cooling tower water in order to avoid system fouling. A licensed and/or trained/experienced plant electrician and millwright-pipe fitter should install this packaged system. Ensure that the concrete pad is level and structurally sound to

Condensate Water Filter Installation Method Statement Read More »

HVAC Method Statements, Method Statements, Piping Method Statements, Piping Works

Installation Method Statement for Crane Gem Rubber Lined Butterfly Valves

These instructions relate only to Crane Gem rubber lined Butterfly valves, which are designed and manufactured to provide isolation, or can be used for regulation, of flow of suitable fluids. Valves must be installed into a well-designed system and it is recommended that the system be inspected in accordance with the appropriate member state legislation.

Installation Method Statement for Crane Gem Rubber Lined Butterfly Valves Read More »

Piping Works, Technical Articles

INSTALLATION, SETTING AND MAINTENANCE INSTRUCTIONS CRANE BALANCING VALVES

SCOPE OF THIS DOCUMENT COVERS BELOW MENTIONED BALANCING VALVES: DM921 & DMG921 DOUBLE REGULATING VALVE (DRV) DM931 & DMG931 DA931 & DAG 931 VARIABLE ORIFICE DOUBLE REGULATING VALVE (VODRV) DM941 & DMG 941 DA941 & DAG941 FIXED ORIFICE DOUBLE REGULATING VALVE (FODRV) FITTING PRESSURE TEST VALVES The pressure test valve with the red tag should

INSTALLATION, SETTING AND MAINTENANCE INSTRUCTIONS CRANE BALANCING VALVES Read More »

Preventive Maintenance, Technical Articles
General Instructions and Method Statement for Chemical Cleaning of Carbon Steel Pipelines

General Instructions and Method Statement for Chemical Cleaning of Carbon Steel Pipelines

Following is a precise chemical cleaning procedure that will ensure the internal and external cleanliness and protection of the pipes before the piping process unit is put into service. Scope of work covers all the horizontal and vertical pipelines through all the areas in the project and buried underground lines in the infrastructure area as

General Instructions and Method Statement for Chemical Cleaning of Carbon Steel Pipelines Read More »

HVAC Method Statements, Piping Works

Technical Requirements of Busbars And Current Carrying Parts of LV Switchgear

The manufacturing of the busbar system shall comply to the latest edition of BS 158 and BS 159. All busbars and current carrying parts shall be manufactured to carry a current density of not more than 1.55 A/mm² and shall be capable of carrying normal current continuously without the temperature rise of any part exceeding

Technical Requirements of Busbars And Current Carrying Parts of LV Switchgear Read More »

Technical Articles
blockset-lv-switchgear

Features & Description of Schneider Electric LV Switchgear Panels

Main Distribution Boards MDB – BLOCKSET The low voltage main distribution boards are Schneider Electric “BLOKSET” range of L.V Switchboards. Blokset switchboards are designed, manufactured and tested in accordance with IEC 60439-1 standards. BLOKSET, a modular multi – functional system has been designed to improve reliability and safety which: Complies with International Standards Tested according

Features & Description of Schneider Electric LV Switchgear Panels Read More »

Technical Articles
SMDB MDB FDB Specifications

Construction & Specification of SMDB, MDB, FDB LV Switchgear Panels & Distribution Board

The switchboards, distribution boards including smbd and control panels are built in accordance with IEC 439 “Factory Built Assemblies for Low Voltage” or BS 5486 “Factory-built Assemblies of Switchgear and Control Gear for Voltage up to and including 1000 AC and 1200V DC. Switchboards SMBD, MDB, FDB are always type tested conforming to tests conducted

Construction & Specification of SMDB, MDB, FDB LV Switchgear Panels & Distribution Board Read More »

Technical Articles
error: Content is protected !!