Site icon Method Statement HQ

Method Statement for Testing & Commissioning of Air Handling Units AHU & FAHU

Prior to testing & commissioning ensure that all the sections of the Air Handling Units are thoroughly cleaned. In case units are supplied with per alumna panels, polythene protective film must be peeled off and must be ensured that no traces of film is left loose within the unit. Only qualified & experienced personnel shall perform testing & commissioning.

Ensure all panels, if removed during installation, are in position. Ensure all electrical wiring carried out and all components are provided with safety protecting and isolating devices. Remove all filters including panel filters: install low efficiency filters such as gauze bags or a set of throw away type filters.

Ensure all dampers are opened. Check water/ steam/ refrigerant coil connection for any leaks. Ensure that all the air in the system and coil is vented out. Check coil face free from free from debris. Add water in condensate drain pan to prime the trap and ensure free flow of water into the drain. Ensure that minimum water levels are maintained in electrical pan humidifier/ air washers.

AHU Fan Start-up Method Statement

General AHU Heat Pipe Commissioning Method

Heat pipe heat exchangers are available for either heat recovery or dehumidification applications. The heat pipes are wrapped around a cooling coil and are known as horseshoe heat pipes. A heat recovery heat pipe is subject to two air streams flowing across either side and transfers heat from on air stream to the other, a horseshoe heat pipe has both of its ends in the same air stream but is located such that the air stream is at different temperature in each location.

In order to measure the performance of a heat pipe, accurate measurements must be taken of airflow velocities and mass/ volume flow rates plus accurate measurements of the temperature of the air streams.

During testing & commissioning the system, ensure that the design conditions have been achieved. Heat pipes, however, operate at a constant effectiveness which can be calculated from the measured data irrespective of the actual conditions. The effectiveness will stay constant as long as the air volume flow rate and velocity remain constant across the heat pipe.

Run Around Coil Heat Recovery

Both a supply and extract air stream flow across the sides/top/bottom of the heat pipe (RAC) and air velocities and volume flow rates may or may not be the same. Accordingly, both air flow rates/ velocities must be measured in order to quantify the performance.

The air volume on either should be measured using a pitot traverse. This can be made on either the entering or leaving air face but should be close to the coil face but a minimum of 50mm away to prevent interference form jetting between the fin surfaces.

Within the AHU, there are a number of cross sectional changes which prevent air velocities from being even. In order to obtain an effective mean value for the velocity across the face of the heat pipe (RAC) the pitot traverse should incorporate at least 9 readings evenly spread across the face of the heat pipe. The air volume flow rate through the heat pipe can be calculated from the product of the mean face velocity and the area of the section.

As the face velocity through the components of the Air Handling Unit will never be even then the temperatures of the air streams throughout the air treatment sections will not be even. Again, a minimum of 9 evenly spread temperature readings should be taken at each measuring plane and a mean value calculated. The required temperature measuring planes for a heat recovery are the entering and leaving face of the supply section and the entering and leaving face of the extract section.

Cooling Coil Test for AHU & FAHU

Explanation of AHU Factory Engineered Controls

Fire Signal: The AHU unit maybe interfaced to fire alarm shut down by connecting a normally closed contact to the designated terminals. If this is not required, the fire contacts are replaced by a link.

Fireman’s Override: Remote fireman’s override switches can be connected to allow operation of the extract fan after a fire alarm has been actuated. Where a mixing box is fitted, the exhaust air damper will be driven to the fully open position while the mixed air and fresh air dampers are driven closed. Override contacts can be connected to the designated terminals where this option has been ordered.

Filter Section: A common or individual filter switch is provided to indicate when the filter section differential pressure is excessive.

Frost Protection Thermostat: A thermostat is provided to switch off the supply fan on units with water coils which prevents the hot water coil from freezing and would typically operate in cold weather if the hot water coil supply has failed.

Fan Section: A pressure differential switch is provided across each fan to provide a proof airflow indication. All fan/ motor are belt and pulley driven.

Heating & cooling Valves: Each actuator is supplied with a flying lead which needs to be connected on site to a connection box fitted on the unit.

Room Temperature Sensor: The room temperature sensor should be wall mounted at a height of approximately 1.5m inside the occupied space of average zone temperature. Do not mount the sensor near a heat source, door, and direct sunlight or in the supply air stream. It requires a single pair of screened cables.

Return Air Temperature Sensor: The return air temperature sensor should be mounted in the common return air duct, ahead of the fan so as to sense the average return air temperature. It requires a single pair screened cables. When possible, the return air temperature sensor should be fitted onto the return air inlet.

Duct Static Pressure Sensor: The duct static pressure sensor should be mounted in the supply ductwork, approximately 2/3 of the distance from the fan to the end of the longest run of ductwork. The sensors require two pairs of screened cable to the control panel. One pair supplies power to the device and the other is the pressure signal from the device to the controller.

Outside Temperature Sensor: The outside temperature sensor should be mounted on north facing wall. It requires a single pair of screened cables. The sensor can be factory mounted in the fresh air inlet.

Exit mobile version