Refrigerant Gas Leakage Detection and Charging Method

The purpose of this AC repair method is to establish a standard procedure for identifying gas leaks on air conditioning and refrigeration system thus preventing release of refrigerant gas in the atmosphere.

This method will also serve as guideline for new and old employees for performing the ac maintenance activity.

The scope of this standard covers all maintenance activities for A/C and refrigeration equipments.

It is the responsibility of the A/C technician to conduct refrigerant leakage testing on the AC and refrigeration system by using standing pressure test and by using bubble test.

Technician shall be competent enough to use the ac gas leakage testing equipment to avoid any damage and to provide the proper result.

Maintenance supervisor and the engineer shall make sure the implementation of this maintenance procedure during routine air-conditioning repair and maintenance works.

Brief Description of Refrigerant Leakage Detection

The best leak checking procedure is the standing pressure test using a pressure source that will not change any appreciable amount with temperature changes.

Nitrogen is a good gas to use for the leakage detection of refrigerant gases.

If the system is pressurized but has less gas, it is recommended also to use the bubble test wherein diluted soap and water is applied to every joints and if bubble is made, gas leak is present on the joints.

Procedure for Refrigerant Leakage Test

Prior to the start of maintenance work, wear safety shoes, goggles, gloves and any other PPE as per project requirements.

Prepare adjustable wrench, nitrogen cylinder, gauge manifold, liquid soap and water.

Follow this procedure when replacing old compressor or when you feel or doubt that system pressure is less with refrigerant gas.

Refer below diagram for guidelines on system set up and making the nitrogen cylinder connections.

Install the nitrogen cylinder hose to the middle portion of the gauge manifold.

Now close the LP side of the gauge manifold.

Isolate the compressor by front seating the suction and the discharge valve of the compressor.

Open the Pressure Reduction Regulator of the Nitrogen Tank.

Open the valve of the HP side of the gauge manifold.

Charge the system with dry nitrogen until pressure reaches 150 psig or as per the equipment maximum rated pressure.

Do not pressurize any system above its working pressure as written on the label of the equipment.

Let the system stand for a while and check the pressure gauge, if the reading falls, there is a leak.

Using diluted water and soap, apply solution to every connecting joint. If bubbles occur, double check visually from where the leakage gas is coming out.

You can also check by visual inspection any leak in the system if traces of oil are present. After confirming presence of oil, conduct bubble test to confirm where exactly the leak is coming from.

Now you can decide about the repair of the joint for smooth operation of the air conditioning system.

Refrigerant Gas Filling / Charging Method

Purpose of this method is to establish a standard maintenance procedure for refrigerant gas checking and charging on Air-conditioning units.

The method will also serve as a guideline for newly hired employees in the company which will be dealing with air conditioning unit maintenance works.

Scope of this standard covers all equipment’s which use refrigerant gas as their cooling agent i.e. including but not limited to Chiller Units, Package Units, Split A/C Units, Cold Store Units, Window AC and fan coil unit maintenance etc.

It is the responsibility of the A/C Technician to check and charge refrigerant gas into the equipment.

Technician shall be competent enough and has a complete background in Air-conditioning system to avoid release of gas into the atmosphere.

The refrigerant gas chemical is considered part of Ozone Depleting Substances ODS, therefore care should be observed when handling these substances.

Maintenance supervisor and the engineer should assure that this maintenance procedure will be followed including the applicable local regulations.

Refrigerant Gas Checking Procedure

Prior to the start of refrigerant charging work, wear necessary PPE i.e. safety shoes, goggles and safety gloves.

Prepare gauge manifold, spanner, adjustable wrench and R-22 or any approved refrigerant gas cylinder.

Open the cover of the access charging valve for both suction and discharge line of the A/C equipment using adjustable wrench.

Connect the LP (Low Pressure) hose of the gauge manifold to the suction side of the refrigerant compressor.

Now connect the HP (High Pressure) hose of the gauge manifold to the suction side of the refrigerant compressor.

If valves are connected after the access charging valve, open the cover of the valve using adjustable wrench and open the valve seat by using spanner.

Open the valve of the gauge manifold to obtain the suction and discharge pressure of the system.

Suction pressure should be 60 to 69 psi while Discharge pressure should be 250 to 275 psi.

For other refrigerant types, please refer to the name plate of the equipment or the compressor for the correct refrigerant charge pressure. Compressor should be running when getting the system refrigerant charge.

Close the valves of the gauge manifold. Close the valve seat of the access charging pin valve if available.

Remove the LP and HP hose of the gauge manifold to the access charging valve of the system.

Refrigerant Gas Charging Procedure

Prior to the start of refrigerant charging work, wear necessary PPE i.e. safety shoes, goggles and safety gloves.

Prepare gauge manifold, spanner, adjustable wrench and R-22 gas cylinder.

Connect the middle hose of the gauge manifold to the refrigerant tank.

Slowly open the valve of the refrigerant tank.

Again, slightly open the threaded connection of the middle hose to purge trapped air then tighten it again.

Open the cover of the access charging valve for both suction and discharge line of the A/C equipment using adjustable wrench.

Connect the LP (Low Pressure) hose of the gauge manifold to the suction side of the refrigerant compressor.

Now connect the HP (High Pressure) hose of the gauge manifold to the suction side of the refrigerant compressor.

If valves are connected after the access charging valve, open the cover of the valve by using adjustable wrench and open the valve seat by using spanner.

Slightly open the valve on the low pressure side of the gauge manifold to charge refrigerant on the suction side of the compressor.

Close the LP valve of the gauge manifold from time to time to check the actual pressure build-up in the compressor. Pressure should be within 60 to 69 psi. Check also the discharge pressure reading. Pressure should be within 250 to 275 psi.

Once the required suction and discharge pressure were obtained, charging can be stopped by shutting the LP valve of the gauge manifold.

Close cylinder or tank valve.

Disconnect cylinder from the gauge manifold.

Close all access charging valves.

Disconnect the gauge manifold to the compressor line.