Site icon Method Statement HQ

Pre Action System Testing and Commissioning Method Statement

Following tools shall be arranged before starting the testing and commissioning of pre action system.

Pre-Commissioning Checks

Before commissioning the system the following shall be ensured:

Commissioning Procedure

Setting Procedure:

Functional Test Procedure (Automatic Operation)

The functional test sequence oft he double interlock  (Automatic) pre action system is as  follows:

Step 1: The system is shown ready for operation.

Step 2: When the smoke detector gets activated cross zoned the smoke detector sends a signal to the pre-action control panel.

Step 3: The pre-action control panel turns into alarm condition and sends a signal to open the solenoid valve. Simultaneously FACP and BMS receives the fire signal (Trouble signal goes to the FACP/BMS at power failure, battery failure and low system pressure in the pre-action control panel) from pre action panel.

Step 3a: Immediately the control signal goes from FACP/BMS to lift control panel at the same time the lift will come down to respective default level within 90 sec., door will open and lift power supply will be shut off.

Step 3b: When the fire sets off a sprinkler pneumatic pressure drops in the dry pilot trim, the Actuator opens which permits water to flow through the drain. This will drain water from the diaphragm Chamber.

Step 4: The open Solenoid valve and dry pilot actuation will release water from the Diaphragm Chamber faster than it can be replenished through the drain restriction in the Automatic Shut-Off Valve.

Step 5: The rapid pressure drop in the Diaphragm Chamber forces the Diaphragm open, allowing air to come out of the sprinklers when the sprinkler bulb breaks open due to the temperature caused frorn fire.

Step 6: The rapid pressure drop in the Diaphragm Chamber forces the Diaphragm open allowing water to enter the system.

Step 7: Water flows through the system to the Water flow pressure alarm switch activating the alarm. Water passes through the trim to the Automatic Shut-off valve to close this valve. Once closed it will prevent the Diaphragm Chamber from becoming inadvertently “Re-Pressurized”, the Automatic Drain Valve is also closed.

Step 8: Water flows through the rest of the system allowing water to spray from the open sprinklers.

Step 9: After fire is under control, Main Control Valve is manually closed  to cut out the water supply. The Diaphram chamber supply Valve is also closed.

Step 10: Then the Main Drain Valve, Alarm Test Valve and the System Drain Valve are opened to drain water from the system.

Step 11: Once the system stops discharging water, close all drains except the Main Drain Valve. Depress the plunger of the Automatic Drain Valve to verify that it is open and the system is drained.

Step 12: Reset the Manual and/or Electric actuation systems. Reset the Solenoid Valve. Clean the Y-strainer in the Diaphragm Chamber Supply connection trim.

Step 13: Open the Diaphragm Chamber Supply Valve so the Diaphragm Chamber can return to full pressure.

Step 14: The Diaphragm will completely close once the Diaphragm Chamber returns to full pressure.

Step 15: Close the Alarm Test Valve. Finally slowly open the main Supply Valve and close the Main Drain Valve once water begins to discharge from the drain.

Step 16: The system is then ready to return for beneficial use.

Functional Test Procedure (Manual Operation)

The functiona l test sequence of the DOUBLE INTERLOCK (Manual ) pre-action system is as follows:

Dry Pilot Actuator Function

The function of the dry pilot actuator is as follows:

Battery Autonomy Test

The pre action panel battery autonomy test was carried out for 24 hrs by removing the permanent AC power supply and keeps the panel alive by battery power.

Exit mobile version