Nitrogen Flushing of Air Conditioning and Refrigeration Systems

Below is the standard procedure for the proper flushing of air-conditioning and refrigeration system with the use of dry nitrogen, and refrigeration equipment which require flushing of the system after exposing it to the atmosphere or during replacement of the refrigerant compressor.

Responsibilities: It is the responsibility of the A/C technician to conduct flushing of the system using dry nitrogen to assure that all soot, contaminants and sludge are removed from the system. He should be competent enough to use this equipment to avoid any damage and to provide the proper result.

Nitrogen Flushing Procedure

  • Prior to the work, wear safety shoes, gloves and goggles.
  • Prepare nitrogen tank with pressure regulator, adjustable wrench, gauge manifold, spanner, tube cutter or hacksaw.
  • This procedure shall be done when replacing old compressor or when system is opened to the atmosphere.
  • Isolate the compressor by front seating the suction and discharge valve. If compressor is for replacement, flushing should be done first before installing the new unit.
  • Use dry nitrogen to push some of the contaminants out of the system by simply attaching the nitrogen regulator to one of the lines and allowing it to blow out the other. Do not exceed the system working pressure with nitrogen. Without compressor in the system, you can safely use 250 psig for high pressure refrigerant systems.Nitrogen Flushing HVAC System 1
  • Disconnect the pipeline before the expansion valve device where a liquid line filter can be installed later.
  • Purge the Nitrogen through the liquid line toward the compressor and discharged out the compressor discharge line before the compressor is connected.Nitrogen Flushing HVAC System 2
  • Disconnect the nitrogen after pushing off all contaminants on this point.
  • Connect the nitrogen to the expansion device side of the liquid line. This line may be purged toward the compressor suction line.

References

  • Refrigeration and Air-conditioning Technology, 3rd Edition By: William C Whitman & William M. Johnson
  • TESDA Refrigeration and Air-conditioning Manual